| Compact thermal-magnetic MCCB | 16–160 A | 18–36 kA | Fixed thermal overload and fixed magnetic short-circuit protection | 2P, 3P, 4P | Small commercial distribution boards, workshops, pumps, and general feeder protection | Simple operation, low maintenance, economical installation, and no auxiliary power required | Long-time and instantaneous settings are usually limited; verify ambient-temperature derating and cable coordination |
| Adjustable thermal-magnetic MCCB | 63–630 A | 25–70 kA | Adjustable thermal overload and adjustable magnetic short-circuit trip | 3P, 4P | Industrial feeders, motor control panels, building distribution, and transformer secondary protection | Better coordination with downstream breakers and greater flexibility for changing loads | Check the available adjustment range, minimum magnetic setting, and coordination study requirements |
| Electronic trip MCCB | 100–1,600 A | 36–100 kA | Electronic L, S, I or L, S, I, G functions; some models include neutral protection | 3P, 4P | Main low-voltage switchboards, data centers, industrial plants, and high-load commercial buildings | Accurate adjustable protection, improved selectivity, event indication, and optional measurement functions | Confirm control-power requirements, sensor rating, electromagnetic compatibility, and battery or display features |
| High-breaking-capacity MCCB | 125–1,600 A | 70–150 kA | Thermal-magnetic or electronic adjustable trip unit | 3P, 4P | Utility incomers, industrial substations, generator outputs, and installations with high prospective fault current | Suitable for systems where the calculated short-circuit current exceeds standard MCCB ratings | High Icu does not automatically equal high Ics; compare both ratings at the actual system voltage |
| Current-limiting MCCB | 63–800 A | 50–150 kA | Fast thermal-magnetic or electronic trip system with current-limiting construction | 2P, 3P, 4P | Dense commercial installations, industrial distribution, and systems requiring reduced let-through energy | Can reduce peak let-through current, arc energy, and mechanical stress on downstream equipment | Verify current-limiting curves, let-through energy, fuse or breaker coordination, and replacement requirements |
| MCCB for motor circuits | 16–800 A | 25–100 kA | Adjustable magnetic protection, motor-compatible overload protection, or coordinated motor-protection arrangement | 3P | Three-phase motors, compressors, conveyors, fans, pumps, and machine-building applications | Can accommodate motor starting current when correctly coordinated with contactors and overload relays | Do not use a standard instantaneous setting without checking inrush current, locked-rotor current, and Type 1 or Type 2 coordination |
| MCCB with earth-fault protection | 100–1,600 A | 36–100 kA | Electronic L, S, I, G trip unit; ground-fault pickup and time delay are adjustable on selected models | 3P, 4P | Large feeders, generators, transformers, commercial mains, and systems requiring improved earth-fault protection | Supports selective ground-fault coordination and can help reduce equipment damage from sustained earth faults | Confirm grounding system, residual-current sensing method, neutral arrangement, and local code requirements |
| Four-pole MCCB with switched neutral | 63–1,600 A | 25–100 kA | Thermal-magnetic or electronic trip unit; neutral pole may be switched and may be protected depending on design | 4P | TT or TN-S systems, transfer switching, generator changeover, mixed single-phase loads, and commercial buildings | Provides simultaneous isolation of three phases and neutral where required by the installation design | Determine whether the neutral is switched, solid, or protected; never assume the neutral-pole rating or operation |
| Three-pole MCCB for balanced three-phase loads | 16–1,600 A | 18–150 kA | Thermal-magnetic or electronic L, S, I trip unit | 3P | Three-phase motors, balanced heaters, industrial feeders, and three-phase distribution circuits without a switched neutral requirement | Efficient use of panel space and straightforward protection for three-phase conductors | Check whether the neutral can carry harmonic or unbalanced current and whether local regulations require neutral isolation |